Heat resistant wire H07G-K tinned

Изображение кабеля Heat resistant wire H07G-K tinned Faber Кabel

Heat resistant wire H07G-K tinned

Использование

For installation in pipes on, in and under plaster as well as in closed cable ducts and for internal wiring of devices, switching and distribution system with ambient temperatures over 55 °C.

Конструкция

Customs Tariff Number (code number) 85444995900000000
Standard DIN EN 50525-2-42 (VDE 0285-525-2-42)
Conductor material tinned copper
Conductor construction Class 5 = flexible
Insulation rubber EI3
Flame-retardant VDE 0482-266-2-4/IEC 60332-3-24 (Cat. C)
UV-resistant yes
Oil-resistant yes
Max. temperature at conductor, °C 110 °C
Permitted outer cable temperature, fixed, °C -40 - +110 °C
Permitted outer cable temperature, moved, °C -25 - +110 °C
Bending radius, fixed installation 6 x Ø
Nominal voltage Uo 450 V
Nominal voltage U 750 V
Number of cores 1
metal base Cu 150 EUR/100 kg
Unit of measurement metre

Стандарты

For installation in pipes on, in and under plaster as well as in closed cable ducts and for internal wiring of devices, switching and distribution system with ambient temperatures over 55 °C.
Артикул Типоразмер кабеля
041438 H07G-K  1X25 VZ  BK
041439 H07G-K  1X35 VZ  BK
041440 H07G-K  1X50 VZ  BK
041441 H07G-K  1X70 VZ  BK
041442 H07G-K  1X95 VZ  BK
041443 H07G-K  1X120 VZ  BK
041444 H07G-K  1X150 VZ  BK
041445 H07G-K  1X185 VZ  BK
041446 H07G-K  1X240 VZ  BK
041447 H07G-K  1X300 VZ  BK
Логотип компании FABER Kabel