(N)A2XSH

Изображение кабеля (N)A2XSH Faber Кabel

Medium voltage cable (N)A2XSH

Использование

For indoor installation and cable ducts for power plant, industrial and distribution networks.

Конструкция

Customs Tariff Number (code number) 85446090000000000
Standard VDE 0276-622 (with ref. to)
Conductor material aluminium
Conductor construction Class 2 = stranded
Insulation XLPE DIX8
Electrical field control inner and outer semiconducting layer (triple extrusion)
Screen Copper wires + counter helix
Sheathing material FRNC-compound HM4
Colour of outer sheath black
Flame-retardant VDE 0482-266-2-4/IEC 60332-3-24 (Cat. C)
Smoke density DIN EN 61034/IEC 61034
Halogen-free DIN EN 50267/IEC 60754
Max. temperature at conductor, °C 90 °C
Permitted outer cable temperature, fixed, °C 70 °C
Permitted outer cable temperature, moved, °C -5 - +70 °C
Bending radius, fixed installation 15 x Ø
Conductor shape (Faber) RMv
Number of cores 1
diameter conductor 21.6 mm
Nominal cross section, sqmm 300 mm²
Conductor resistance 0.1 Ohm/km
Insulation wall thickness 5.5 mm
Ampacity in air (30 °C) 496 A
Short-circuit current (1 s) 28.2 kA
Wall thickness of sheath 2.5 mm
Bending radius, fixed installation 615 mm
outer diameter approx. 41.00 mm
Tensile strength (during installation) 9000 N
Aluminium weight (GER) 870
metal base Al (ger) 0 EUR/100 kg
Copper weight (GER) 283
metal base Cu 0 EUR/100 kg
net weight per 1000 2050 kg
Unit of measurement metre

Стандарты

For indoor installation and cable ducts for power plant, industrial and distribution networks.
Артикул Типоразмер кабеля
015264 (N)A2XSH 1X300/25 12/20 kV BK
Логотип компании FABER Kabel