(N)HXH FE180/E90

Изображение кабеля (N)HXH FE180/E90 Faber Кabel

FRNC power cable (N)HXH FE180/E90

Использование

For installation in dry and wet rooms, also for direct bedding in concrete, but not for direct burial in the ground and not for use in water. The cable has improved properties in case of fire and may be used in public buildings with high safety requirements. The cable is halogen-free, has a low smoke density and is fire-resistant according to VDE 0472 part 814 (180 min., = IEC 60331), EN 50200 and EN 50362. Furthermore the cable passed the test of 90 min. circuit integrity according to DIN 4102 part 12 (E 90) for all so-called standard installation systems (ladder, tray and ceiling). A special test certificate about the circuit integrity is issued by -The Civil Engineering Materials Testing Institute-. For calculation of electrical systems with circuit integrity has to be considered that electrical resistance of copper conductors at 1000 °C is approximately 4,5 times higher than at 20 °C and the current carrying capacity has to be reduced respectively.

Конструкция

Customs Tariff Number (code number) 85444995900000000
Standard VDE 0266
Conductor material copper, bare
Conductor construction class 1, from 25 sqmm class 2
Insulation FRNC-compound HI1
Sheathing material FRNC-compound HM1
Colour of outer sheath orange
Flame-retardant VDE 0482-266-2-4/IEC 60332-3-24 (Cat. C)
Smoke density DIN EN 61034/IEC 61034
Halogen-free DIN EN 50267/IEC 60754
Fire-resistant VDE 0472-814/IEC 60331-11 (FE 180)
Circuit integrity E90
Max. temperature at conductor, °C 90 °C
Permitted outer cable temperature, fixed, °C -30 - +90 °C
Permitted outer cable temperature, moved, °C -5 °C
Bending radius, fixed installation, multicore 12 x Ø
Conductor shape round
Colour of outer sheath orange
metal base Cu 0 EUR/100 kg
Unit of measurement metre

Стандарты

For installation in dry and wet rooms, also for direct bedding in concrete, but not for direct burial in the ground and not for use in water. The cable has improved properties in case of fire and may be used in public buildings with high safety requirements. The cable is halogen-free, has a low smoke density and is fire-resistant according to VDE 0472 part 814 (180 min., = IEC 60331), EN 50200 and EN 50362. Furthermore the cable passed the test of 90 min. circuit integrity according to DIN 4102 part 12 (E 90) for all so-called standard installation systems (ladder, tray and ceiling). A special test certificate about the circuit integrity is issued by -The Civil Engineering Materials Testing Institute-. For calculation of electrical systems with circuit integrity has to be considered that electrical resistance of copper conductors at 1000 °C is approximately 4,5 times higher than at 20 °C and the current carrying capacity has to be reduced respectively.
Артикул Типоразмер кабеля
010951 (N)HXH-J E90 3X1.5 RE OG
010952 (N)HXH-J E90 3X2.5 RE OG
010953 (N)HXH-J E90 3X4 RE OG
010954 (N)HXH-J E90 3X6 RE OG
010955 (N)HXH-J E90 3X10 RE OG
010956 (N)HXH-J E90 3X16 OG
010957 (N)HXH-J E90 4X1.5 RE OG
010958 (N)HXH-J E90 4X2.5 RE OG
010959 (N)HXH-J E90 4X4 RE OG
010960 (N)HXH-J E90 4X6 RE OG
010961 (N)HXH-J E90 4X10 RE OG
010962 (N)HXH-J E90 4X16 OG
010963 (N)HXH-J E90 4X25 RM OG
010964 (N)HXH-J E90 4X35 RM OG
010965 (N)HXH-J E90 5X1.5 RE OG
010966 (N)HXH-J E90 5X2.5 RE OG
010967 (N)HXH-J E90 5X4 RE OG
010968 (N)HXH-J E90 5X6 RE OG
010969 (N)HXH-J E90 5X10 RE OG
010970 (N)HXH-J E90 5X16 OG
010971 (N)HXH-J E90 5X25 RM OG
010989 (N)HXH-J E90 7X1.5 RE OG
011020 (N)HXH-J E90 12X1.5 RE OG
011124 (N)HXH-J E90 7X2.5 RE OG
011162 (N)HXH-J E90 24X1.5 RE OG
011177 (N)HXH-O E90 1X150 RM OG
011178 (N)HXH-O E90 1X300 RM OG
011744 (N)HXH-O E90 1X120 RM OG
011754 (N)HXH-O E90 1X240 RM OG
011755 (N)HXH-O E90 1X185 RM OG
011756 (N)HXH-O E90 1X95 RM OG
011757 (N)HXH-O E90 1X50 RM OG
011843 (N)HXH-O E90 1X70 RM OG
011869 (N)HXH-J E90 4X150 RM OG
011949 (N)HXH-J E90 4X95 RM OG
011950 (N)HXH-J E90 04X50 RM OG
011955 (N)HXH-J E90 4X70 RM OG
011956 (N)HXH-J E90 4X120 RM OG
011963 (N)HXH-J E90 4X240 RM OG
011982 (N)HXH-J E90 12X2.5 RE OG
012011 (N)HXH-O E90 2X1.5 RE OG
012020 (N)HXH-O E90 1X16 OG
012021 (N)HXH-O E90 1X25 RM OG
012022 (N)HXH-O E90 1X35 RM OG
012221 (N)HXH-O E90 1X400 RM OG
012928 (N)HXH-J E90 7X6 RE OG
013128 (N)HXH-J E90 10X1.5 RE OG
013223 (N)HXH-O E90 2X4 RE OG
013224 (N)HXH-O E90 2X6 RE OG
013225 (N)HXH-O E90 2X10 RE OG
013226 (N)HXH-O E90 2X16 RE OG
013293 (N)HXH-J E90 7X4 RE OG
013666 (N)HXH-J E90 4X185 RM OG
013667 (N)HXH-J E90 5X35 RM OG
013668 (N)HXH-J E90 5X70 RM OG
013669 (N)HXH-J E90 5X95 RM OG
013670 (N)HXH-J E90 5X150 RM OG
013671 (N)HXH-J E90 5X185 RM OG
013885 (N)HXH-O E90 2X2.5 RE OG
013912 (N)HXH-O E90 4X95 RM OG
013913 (N)HXH-O E90 4X120 RM OG
014073 (N)HXH-J E90 3X25 RM OG
014074 (N)HXH-J E90 3X35 RM OG
014075 (N)HXH-J E90 3X50 RM OG
014076 (N)HXH-J E90 3X70 RM OG
014077 (N)HXH-J E90 5X120 RM OG
015730 (N)HXH-O E90 1X16 RM OG